Online UPS

> Products > Online UPS > PlusIII LV Tower Series
1000VA to 3000VA

PlusIII LV Tower Series
1000VA to 3000VA


The PlusIII LV Tower Series 1000VA to 3000VA is a true double conversion online UPS with pure sinewave output and zero transfer time in a compacted stand-alone unit. Featuring 1000VA, 3000VA configuration with wide AC input range, output power factor 0.9, LCD display, high performance and optional external battery bank, PlusIII LV Tower Series stand out as high efficient line of online UPS for mission critical equipment and industrial applications in long time operation or harsh mains conditions.
 

* High performance true double conversion On Line UPS 1000VA to 3000VA
* Individual power distribution unit (PDU) maintenance bypass switch
* Intelligent Slot (SNMP) + USB multiple communications
* External battery bank to extend back-up time (Optional for PlusIII-1KLBE/PlusIII-3KLBE)
* Microprocessor control guarantees high reliability
* Low heat dissipation in long time operation
* Emergency power-off function (EPO)
* Automatic self-testing function
* High efficiency mode (ECO mode)  
* Output voltage regulation < 2%
* Power management software
* Output power factor 0.9
* Wide input range 
* Fan speed control
* DC start

MODEL PlusIII-1KLB PlusIII-1KLBE PlusIII-3KLB PlusIII-3KLBE
CAPACITY 1KVA/0.9KW 1KVA/0.9KW 3KVA/2.7KW 3KVA/2.7KW
INPUT
Voltage 1 Phase 2 Wires with Ground 100/110/115/120Vac or 200/208/220Vac
Voltage Range 100/110/115/120Vac: 55-150Vac ; 200/208/220Vac: 110-300Vac
Frequency  50Hz or 60Hz (Auto-Sensing)
THDi < 5% at full load
OUTPUT
Voltage  100/110/115/120Vac or 200/208/220Vac
Voltage Regulation 100/110/115/120Vac: < 1% ; 200/208/220Vac: +/- 2%
Frequency ( Battery Mode) 100/110/115/120Vac: 50Hz or 60Hz +/- 0.1Hz ; 200/208/220Vac: 50Hz or 60Hz +/- 0.2Hz
Waveform Pure Sinewave
THD 100/110/115/120Vac: < 4%(linear load), < 8%(non-linear load) ; 200/208/220Vac: < 3%(linear load), < 5%(non-linear load) 
Crest Ratio 3 : 1
EFFICIENCY
To AC Mode 100/110/115/120Vac: > 89% at full load and battery full charged ; 200/208/220Vac: > 88%
To Battery Mode 100/110/115/120Vac: > 85% at full load and battery full charged ; 200/208/220Vac: > 85%
To ECO Mode 100/110/115/120Vac: > 95% at full load and battery full charged ; 200/208/220Vac: > 93%
BATTERY
Voltage 36VDC 100/110/115/120Vac: 72VDC ; 200/208/220Vac: 96VDC
Type 12V/7AH*3pcs Extendable  72VDC: 12V/9AH*6pcs
96VDC: 12V/7AH*8pcs
Extendable
Recharge Time 5 hours to 90%

Depend on capacity

of external battery

5 hours to 90%

Depend on capacity

of external battery

TRANSFER TIME
Line Mode to Battery Mode 0ms 
Inverter to Bypass, ECO Mode < 4ms
ECO Mode to Inverter < 10ms
DISPLAY
LCD Display

Input, Output, Load, Battery, Mode/Fault/Warning code, Inverter operating, Bypass operating,

Output voltage and frequency and Bypass disable/enable selection information

AUDIBLE ALARM
Battery Mode Beeps Every 4 Seconds
Low Battery Sounding Every  Second
Overload Sounding Twice Every  Second 
Fault Beeping continuously
COMMUNICATIONS
Interface (Port) USB Port
Intelligent Slot Slot for SNMP or AS400 card (Optional)
EPO Emergency Power Off
ENVIRONMENT
Operating Temperature 100/110/115/120Vac: 0-40℃; 200/208/220Vac:0° C - 45° C
Humidity 20-90% (Non-condensing)
Acousitc Noise 100/110/115/120Vac: <45dB at 1M ; 200/208/220Vac: <50dB at 1M
PHYSICAL
Dimension (D*W*H) 420*145*230mm 560*193*346mm

PlusIII LV Tower Series 1000VA to 3000VA     Brochure     Download

PlusIII LV Tower Series 1000VA to 3000VA     Manual        Download