Online UPS

> Products > Online UPS > PlusI ISO Tower Series
6000VA to 10000VA

PlusI ISO Tower Series
6000VA to 10000VA


The PlusI ISO Tower Series 6000VA to 10000VA is a true double conversion online UPS with pure sinewave output and zero transfer time and enhanced capacity. Main UPS, isolation transformer and battery in a split box makes this UPS flexible to comply with the demand of single output voltage, or dual output voltage, or long-time operation. Featuring 6000VA, 10000VA integrated with LCD display, high output power factor 0.9, outstanding performance, optional isolation transformer box and optional external battery bank, PlusI ISO Tower Series stand out as high efficient line of online UPS for mission critical equipment and industrial applications in long time operation or harsh mains conditions.
 

* High performance true double conversion Online UPS 6000VA to 10000VA 
* Microprocessor control guarantees high reliability
* External battery box to extend backup time (Optional for PlusI-6KLBE(-ISO)/PlusI-10KLBE(-ISO))
* Isolation transformer in split box for dual output voltage (Optional for PlusI-6KLB(E)-ISO/PlusI-10KLB(E)-ISO)
* Power distribution unit (PDU) maintenance bypass switch 
* Low heat dissipation in long time operation
* Input THDi < 5% / Output THD < 2%
* Emergency power-off function (EPO)
* High efficiency mode (ECO mode)  
* Fan speed control & DC start
* Output voltage regulation < 1%
* Automatic self-testing function
* Power management software
* Output power factor 0.9

MODEL PlusI-6KLB(-ISO) PlusI-6KLBE(-ISO) PlusI-10KLB(-ISO) PlusI-10KLBE(-ISO)
CAPACITY 6KVA/5.4KW 6KVA/5.4KW 10KVA/9KW 10KVA/9KW
INPUT
Phase 1 Phase 2 Wires with Ground
Voltage  220/230/240Vac
Frequency  50Hz or 60Hz (Auto-Sensing)
THDi < 5% with R full load
OUTPUT
Phase PlusI-6KLB(E)/ PlusI-10KLB(E): 1 Phase 2 Wires with Ground
PlusI-6KLB(E)-ISO/ PlusI-10KLB(E)-ISO: 1 Phase 3 Wires with Ground
Voltage  PlusI-6KLB(E)/ PlusI-10KLB(E): 220/230/240Vac
PlusI-6KLB(E)-ISO/ PlusI-10KLB(E)-ISO: 220/110Vac, 230/115Vac, or 240/120Vac (set via control panel)
Voltage Regulation PlusI-6KLB(E)/ PlusI-10KLB(E): +/-1%
PlusI-6KLB(E)-ISO/ PlusI-10KLB(E)-ISO: +/-2%
Frequency ( Battery Mode) 50Hz or 60Hz +/- 0.05Hz
Waveform Pure Sinewave
THD < 2% (linear load), < 5% (non-linear load) 
Crest Ratio 3 : 1
EFFICIENCY
To AC Mode > 92% at full load and battery fully charged
To Battery Mode > 92% at full load and 12VDC/battery
To ECO Mode > 96% at full load and battery fully charged
BATTERY
Voltage 240VDC
Type 12V/7AH*20pcs Extendable  12V/9AH*20pcs Extendable
Recharge Time 7 hours to 90%

Depend on capacity

of external battery

7 hours to 90%

Depend on capacity

of external battery

TRANSFER TIME
Line Mode to Battery Mode 0ms 
Inverter to Bypass 0ms
ECO Mode to Inverter < 10ms
DISPLAY
LED Indicator Normal (Green), Bypass (Yellow), Fault (Red), Battery (Yellow)
LCD Display

Load level, Battery voltage, Battery mode, AC mode, Bypass mode information

AUDIBLE ALARM
Battery Mode Beeps Every 4 Seconds
Low Battery Sounding Every Second
Overload Sounding Twice Every Second 
Fault Beeping continuously
COMMUNICATIONS
Interface (Port) Dry Contact (Optional) ; USB Port
Intelligent Slot Slot for SNMP or AS400 card (Optional)
EPO Emergency Power Off
ENVIRONMENT
Operating Temperature 0° C - 40° C (32° F - 104° F)
Humidity 0-95% (Non-condensing)
Acousitc Noise <50 dB at 1M
PHYSICAL
Main UPS (D*W*H) 623*192*347mm
Isolation Box with PDU (D*W*H) 623*192*347mm
Battery Box (D*W*H) 623*192*347mm

PlusI ISO Tower Series 6000VA to 10000VA     Brochure     Download

PlusI ISO Tower Series 6000VA to 10000VA     Manual        Download